Lithium Solar Battery Calculator

A lithium solar battery calculator should give a smaller number than a generic one, and this one does, because lithium chemistries such as LiFePO4 can be safely discharged much deeper than lead-acid. Enter your load, backup hours and system voltage, and the tool applies a lithium depth of discharge to show the amp-hours and kilowatt-hours you actually need. It is free, works without an account and keeps everything in your browser.

FreeNo signupNothing uploaded or stored

What the battery must do

Total watts of everything on the battery at once

How long the load must run

Battery chemistry and voltage

Match your inverter's battery voltage

Sets the usable depth of discharge

Lithium ≈ 0.85, lead-acid ≈ 0.5. Editable from your datasheet.

How many batteries?

From the label of the model you plan to buy

Battery capacity needed

0 Ah

at 48 V, lithium DoD 0.85

Bank size

0.00 kWh

0.00 kWh usable ÷ 0.85

Usable energy required

0.00 kWh

0 W × 4 h

Batteries to buy

-

Enter one battery's Ah above

Formula: Ah = load W × hours ÷ system V ÷ DoD. Series count = system V ÷ battery V; parallel strings = ⌈required Ah ÷ battery Ah⌉.

How to use the lithium solar battery calculator

  1. Enter the load in watts that the battery must support. For whole-house backup, total only the circuits that stay on during an outage.
  2. Set the backup hours you want, remembering that lithium banks are often sized for a full evening or overnight rather than a short cut.
  3. Choose the battery voltage your inverter expects. Many lithium home batteries are 48V, while small systems use 12V or 24V.
  4. Leave the chemistry on lithium and, if your battery datasheet quotes a different recommended depth of discharge, adjust it to match.
  5. Compare the result in kilowatt-hours with the models you are considering, since lithium batteries are usually sold by kWh rather than Ah.

What to include

  • The load in watts and the hours it must run, as with any battery sizing
  • The recommended depth of discharge from your battery's datasheet, usually between 0.8 and 0.9
  • The nominal voltage, which for a LiFePO4 pack is often 12.8V, 25.6V or 51.2V
  • The continuous discharge current limit of the battery, so one unit can actually feed your inverter
  • Whether the battery management system allows parallel connection if you need more than one
  • Any plan to add capacity later, as mixing old and new lithium units is not always supported

Why lithium sizing comes out smaller than lead-acid

The formula is unchanged: Ah = (watts × hours) ÷ voltage ÷ depth of discharge. What changes is the last term. A lead-acid battery that is regularly taken below half charge loses cycle life quickly, so the usable fraction is about 0.5. Lithium iron phosphate cells tolerate discharge to about 80 to 90 percent of rated capacity, so the usable fraction is roughly 0.85. The same energy need therefore requires about 40 percent fewer rated amp-hours in lithium.

Say you type 1,000 W for 6 hours on a 48V system. That is 6,000 Wh, or 125 Ah at 48V, and at a 0.85 depth of discharge the answer is about 147 Ah, which is a 7 kWh class battery. The calculator presents both figures so you can match whichever unit the supplier uses.

Reading a lithium battery datasheet

Three numbers matter beyond capacity. The nominal voltage tells you whether the pack suits your inverter. The continuous discharge current, in amps, must be at least your peak load divided by the voltage, otherwise the battery management system will cut out under load even if the capacity is fine. And the cycle-life rating at a stated depth of discharge tells you how conservative to be with the DoD you type into the tool. A pack rated for thousands of cycles at 80 percent is fine at 0.8.

Frequently asked questions

What depth of discharge should I use for LiFePO4?

Most manufacturers recommend somewhere between 80 and 90 percent of rated capacity for daily cycling. The calculator defaults to that range; if your datasheet says otherwise, type the datasheet value.

Is a lithium battery sold in Ah or kWh?

Both appear in listings. Home storage units are usually described in kWh, while 12V and 24V packs for small systems are often listed in Ah. The tool shows both so you can compare directly.

Can I mix lithium and lead-acid batteries in one bank?

No. They charge at different voltages and the inverter can only follow one profile. Size the bank for a single chemistry.

Does the calculator handle a 48V lithium battery?

Yes. Select 48V as the system voltage and the amp-hours drop to a quarter of the 12V figure for the same energy, which is why larger systems use higher voltage.

Is this calculator free to use?

Yes, completely. There is no signup, no limit on how many times you run it and no data leaves your device.