Solar Battery Backup Time Calculator

This battery backup time calculator works the sizing formula in reverse. You already have a battery, or a quote for one, and you want to know how many hours it will keep a given load running. Enter the amp-hour rating, the voltage, the load in watts and the chemistry, and the tool gives you a realistic run time rather than the optimistic one printed on the box. Free, no signup, nothing stored.

FreeNo signupNothing uploaded or stored

What the battery must do

Label figure; add Ah for parallel strings

Nominal; add volts for series strings

Watts drawn while on battery

Battery chemistry and voltage

Sets the usable depth of discharge

Lithium ≈ 0.85, lead-acid ≈ 0.5. Editable from your datasheet.

Backup time

-

0 Wh usable ÷ 0 W

Stored energy

0.00 kWh

0 Ah × 12 V

Usable energy

0.00 kWh

× 0.85 DoD (lithium)

Formula: backup hours = Ah × V × DoD ÷ load W.

How to use the solar battery backup time calculator

  1. Enter the battery capacity in amp-hours exactly as printed on the label, and the nominal voltage of the battery or bank, such as 12V or 48V.
  2. If you have several batteries, enter the total bank capacity: add amp-hours for parallel strings, keep amp-hours and add voltage for series strings.
  3. Type the load you intend to run in watts. Use the appliance load calculator if you need to add up several devices.
  4. Select lithium or lead-acid so the calculator uses only the usable portion of the capacity, not the full label figure.
  5. Read the backup time in hours and minutes, then try a smaller load to see how much longer the battery lasts if you switch off the heavy items.

What to include

  • The amp-hour rating and voltage from the battery label, not a guess
  • Whether the batteries are wired in series, parallel or both, because that changes the bank figure
  • The actual watts you will draw, including the inverter's own idle consumption if you know it
  • The chemistry, since a lead-acid battery gives roughly half its label capacity before it should be recharged
  • The age of the battery, as older banks hold less than their original rating
  • How full the battery is when the outage starts, if it is not always at 100 percent

The backup time formula and why label capacity misleads

Backup hours = Ah × V × depth of discharge ÷ load in watts. The first two terms give the energy stored in watt-hours. The depth of discharge trims that to what you can actually use without shortening the battery's life: around 0.8 to 0.9 for lithium, around 0.5 for lead-acid. Dividing by the load gives the hours it will run.

Say you type a 200 Ah, 12V lead-acid battery and a 300 W load. Energy is 2,400 Wh, usable energy at 0.5 is 1,200 Wh, and 1,200 ÷ 300 gives 4 hours. The same 200 Ah in lithium at 0.85 would give about 6.8 hours. Many people are disappointed by their backup time simply because they expected the full 2,400 Wh and got half of it, which is normal for lead-acid and not a fault.

Ways to stretch the hours you already have

If the run time is shorter than you hoped, the cheapest fix is on the load side. Swapping a few bulbs for LEDs, running one fan instead of three, or keeping the fridge door shut can cut the draw by a third. Re-run the calculator with the smaller load to see the effect before spending anything on more batteries. Adding capacity in parallel is the other route; two identical batteries double the hours.

Frequently asked questions

How long will a 200Ah battery run a fan and lights?

It depends on the voltage and chemistry. Type 200 Ah, your battery voltage, the combined watts of the fan and lights, and the chemistry, and the tool shows the hours. A small load of under 150 W on a 12V lithium battery typically runs through the night.

Why is my real backup time less than the calculator says?

Usually because the battery is older than its label suggests, the inverter has its own idle draw, or the load is higher than you estimated. Measure the draw with a plug-in meter if you can and re-enter it.

Does the tool account for inverter losses?

Not by default. Inverters waste a small share of energy as heat, so if you want a safer number add that share to the load you type, or treat the result as an upper limit.

Can I enter two batteries in parallel?

Yes. Enter the combined amp-hours. Two 100 Ah batteries in parallel are 200 Ah at the same voltage; two in series are 100 Ah at double the voltage.

Do I need an account to use this?

No. There is no signup, no email and no saved history. Open the page, type your figures and read the result.